User Manual Smart-UPS. Rack-Mount 2U. 1 Introduction The APC™ by Schneider Electric Smart-UPS™ product name is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations. On this page you find the APC Smart-UPS 1000VA manual. Please read the instructions in this operator manual carefully before using the product. If you have any questions about your that are not answered in the manual, please share your question in the troubleshooting section on the buttom of this page. User’s Manual English APC Smart-UPS® 1000VA/1500VA 230VAC/120VAC/100VAC 750XL/1000XL 230VAC/120VAC Tower Uninterruptible Power Supply 990-1062A 11/01. Mxr m116 fullbore metal distortion pedal user manual video. Summary of Contents of user manual for APC Smart UPS 750 VA SUA750. Page 1User Manual English APC Smart-UPS® 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005. From the utility line. The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is fully discharged. 1: INSTALLATION The User Manual and Safety Guide are accessible on the supplied User Manuals CD and on the APC web site, www.apc.com.
Summary of the content on the page No. 1
User Manual
English
®
APC Smart-UPS
750/1000/1500 VA
100/120/230 Vac
2U Rack-Mount
Uninterruptible Power Supply
990-1194C 07/2008
Summary of the content on the page No. 2
Summary of the content on the page No. 3
Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags, and surges from reaching your computer and other valuable electronic equipment. The UPS filters small utility line fluctuations and isolates your equipment from large disturbances by internally dis- connecting from the utility line. The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is discharged. 1: INSTALLATION
View and Download Samsung SM-S766C user manual online. User manual sprint wireless sm-n900p galaxy note 3 jb english user manual ver.mi6f6 (english(north america)) (209 pages) Cell Phone Samsung SM-T2105 User Manual (94 pages). Summary of Contents for Samsung SM-S766C. Jan 15, 2017 The Samsung Galaxy Stardust manual aka Samsung SM-S766C user guide (TracFone) is available now. The manual is available in pdf format and support in englis language. The device is powered by 1.2 GHz Dual-Core Processor. It has 3.97 inch main display with 400 x 800 pixelsresolution. It's equipped with 5 MP rear camera. Samsung sm s766c battery. Get access to helpful solutions, how-to guides, owners' manuals, and product specifications for your Galaxy Stardust (TracFone) from Samsung US Support.
Summary of the content on the page No. 4
Positioning the UPS Place the UPS where it will be used. The UPS is heavy. Select a location sturdy enough to handle the weight. Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the specified limits. 0º- 40ºC (32º-104ºF) 0-95% Relative Humidity PLACEMENT 2.5 cm (1 in.) Mounting the UPS in a Rack The UPS is heavy. To lighten it, you may remove the battery before mounting the unit in the rack (Steps 1 and 2). Step 1 Step 2 Caution
User manual pdf. I figured out what went wrong and how to fix it.When Opera Beta was installed from cli apt-get it screwed up my keyboard shortcut keys (which I hadn't changed at all from default) and the only hint I had was the new tab opening when I tried Fn+Up arrow. I was unable to type anything.
Summary of the content on the page No. 5
Installing and Connecting the Battery and Attaching the Front Bezel Step 1 Step 2 Step 3 Step 4 Connect battery plug to UPS. Tuck white battery cord into space above connector. Connecting Equipment and Power to the UPS SMART-UPS REAR PANEL 100/120V Models 120V Model Only: Site wiring fault indicator 230V Models 3
Summary of the content on the page No. 6
1. Connect equipment to the UPS. Note: Do not connect a laser printer to the UPS. A laser printer draws significantly more power than other types of equipment and may overload the UPS. 2. Add any optional accessories to the Smart-Slot. 3. Using a power cord, plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. 100V/120V models: The power cord is permanently attached to the rear panel of the UPS. The INPUT plug is a NEMA 5-15P. 230V models
Summary of the content on the page No. 7
2: OPERATION SMART-UPS FRONT PANEL Power On Power Off Online The online LED illuminates when the UPS is supplying utility power to the connected equipment. If the LED is not lit, the UPS is either not turned ON, or is supplying battery power. This LED illuminates to indicate the UPS is compensating for a high AVR Trim utility voltage. This LED illuminates to indicate the UPS
Summary of the content on the page No. 8
Replace Battery Failure of a battery self-test causes the UPS to emit short beeps for one minute and the replace battery LED illuminates. Refer to Trouble- shooting in this manual. The replace battery LED flashes and short beep is emitted every two Battery seconds to indicate the battery is disconnected. Disconnected The UPS performs a self-test automatically when turned on, and every Automatic Self-Test two weeks thereafter (by default). During the self-test, the UPS briefly oper
Summary of the content on the page No. 9
3: USER CONFIGURABLE ITEMS NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT ACCESSORY CARDS. FACTORY USER SELECTABLE FUNCTION DESCRIPTION DEFAULT CHOICES Automatic Self-Test Every 14 days Every 7 days This function sets the interval (336 hours) (168 hours), at which the UPS will execute On Startup Only, No a self-test. Refer to your soft- Self-Test ware manual for details. UPS ID UPS_IDEN Up to eight characters to Use this field to uniquely defi
Summary of the content on the page No. 10
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT ACCESSORY CARDS. FACTORY USER SELECTABLE FUNCTION DESCRIPTION DEFAULT CHOICES Low Battery Warning. Brightly lit: Low battery The low battery warning warning interval is about beeps are continuous when PowerChute interface two minutes. two minutes of run time re- software provides auto- Dimly lit: Low battery main. matic, unattended shut- warning interval is about down when approximately You can
Summary of the content on the page No. 11
4: STORAGE, MAINTENANCE, AND TRANSPORTING Storage Store the UPS covered and positioned as for proper functioning, in a cool, dry location, with the bat- teries fully charged. At -15 to +30 °C (+5 to +86 °F), charge the UPS battery every six months. At +30 to +45 °C (+86 to +113 °F), charge the UPS battery every three months. Replacing the Battery Module This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You
Summary of the content on the page No. 12
5: TROUBLESHOOTING Use the chart below to solve minor Smart-UPS installation and operation problems. Refer to the APC web site, www.apc.com, for assistance with complex UPS problems. PROBLEM AND POSSIBLE SOLUTION CAUSE UPS WILL NOT TURN ON Battery not connected prop- Check that the battery connector is fully engaged. erly. button not pushed. Press the button once to power the UPS and the connected equipment. UPS not connected to utility Check that the power cable from the UPS to t
Summary of the content on the page No. 13
PROBLEM AND POSSIBLE SOLUTION CAUSE THE OVERLOAD LED IS LIT AND THE UPS EMITS A SUSTAINED ALARM TONE The UPS is overloaded. The connected equipment exceeds the specified maximum load as de- fined in Specifications at the APC web site, www.apc.com. The alarm remains on until the overload is removed. Disconnect nonessen- tial equipment from the UPS to eliminate the overload. The UPS continues to supply power as long as it is online and the circuit breaker does not trip; the UPS will no
Summary of the content on the page No. 14
Apc Be750g Manual
PROBLEM AND POSSIBLE SOLUTION CAUSE THERE IS NO UTILITY POWER AND THE UPS HAS BEEN TURNED OFF 120V/230V Models: When the Press and hold the button, (for about 3 seconds). The unit will UPS is off and there is no utility beep, the LED lights will flash, and the unit will beep a second time. power, use the cold start feature to Release the ON button during the second beep. This will supply imme- apply power to the connected diate power to the UPS and the connected equipment. Make s
Summary of the content on the page No. 15
Service If the UPS requires service do not return it to the dealer. Instead, follow these steps: 1. Review the problems discussed in the Troubleshooting section of this manual to eliminate com- mon problems. 2. If the problem persists, contact APC Customer Service through the APC web site, www.apc.com/support. ! Note the model number of the UPS, the serial number, and the date purchased. If you call APC Customer Service, a technician will ask you to describe the problem and try to solve
Summary of the content on the page No. 16
6: REGULATORY AND WARRANTY INFORMATION Regulatory Agency Approvals and Radio Frequency Warnings 230V MODELS This is a Class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take corrective actions. 120V MODELS This equipment has been tested and found to comply with the limits for a Class A digital device, pur- suant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
Summary of the content on the page No. 17
Declaration of Conformity Limited Warranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole op- tion, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Products must be returned with transportat
American Power Conversion Corporation (APC) is the leading national and international manufac-
turer of state-of-the-art uninterruptible power supplies, redundant switches, power management soft-
ware, and related equipment. APC products protect hardware, software, and data from power distur-
bances in business and government offices throughout the world.
Apc Smart Ups 750 2u
The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags,
and surges from reaching your computer and other valuable electronic equipment. The UPS filters
small utility line fluctuations and isolates your equipment from large disturbances by internally dis-
connecting from the utility line. The UPS provides continuous power from its internal battery until
the utility line returns to safe levels or the battery is discharged.
Read the Safety Instruction sheet before installing the UPS.
Inspect the UPS upon receipt. APC designed robust packaging for your product. However, accidents
and damage may occur during shipment. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents. The package contains the UPS, a literature kit containing one CD, one
serial cable, one USB cable, product documentation and Safety Information.
Apc Smart Ups 750 Manuale Italiano
230V models: Two IEC jumper cables are included and a utility connector plug is included for use
Apc Smart Ups 750 Xl
on servers with permanently attached power cords.
Apc Smart Ups 750 Manual
The UPS is shipped with the battery disconnected.
Positioning the UPS
The UPS is heavy. Select a location sturdy enough to handle the weight.
Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the
P
1in
0º- 40ºC (32º-104ºF)
Humidity